§ 141.560. Is my system subject to individual filter turbidity requirements?.

Code of Federal Regulations

Title 40. Protection of Environment

Chapter I. ENVIRONMENTAL PROTECTION AGENCY

Subchapter D. WATER PROGRAMS

Part 141. NATIONAL PRIMARY DRINKING WATER REGULATIONS

Subpart T. ENHANCED FILTRATION AND DISINFECTION-SYSTEMS SERVING FEWER THAN 10,000 PEOPLE

INDIVIDUAL FILTER TURBIDITY REQUIREMENTS

Current through July 3, 2019

§ 141.560. Is my system subject to individual filter turbidity requirements?

If your system is a subpart H system serving fewer than 10,000 people and utilizing conventional filtration or direct filtration, you must conduct continuous monitoring of turbidity for each individual filter at your system. The following requirements apply to continuous turbidity monitoring:

(a) Monitoring must be conducted using an approved method in §141.74(a);
(b) Calibration of turbidimeters must be conducted using procedures specified by the manufacturer;
(c) Results of turbidity monitoring must be recorded at least every 15 minutes;
(d) Monthly reporting must be completed according to §141.570; and
(e) Records must be maintained according to § 141.571.

Cite as 40 C.F.R. § 141.560